- Coolant as the core unit in the container water cooling system, it is recommended to follow up and test regularly, at least once a year (pH value is tested once every six months).
- Coolant procurement needs to focus on the relevant parameters in Table 3.1, and needs to be considered as appropriate when the requirements are not met.
- Regular testing of coolant focuses on pH value, when the pH value is lower than 7 then it is not recommended (pH indicator can be added to the coolant, when the pH is lower than 8, the coolant will change color to facilitate observation); the testing method is shown in the following table.
- Regular testing of coolant is followed by concern for freezing point, glycol ratio, total hardness, etc.; at a later stage, attention should be paid to whether the content of Al, Fe, Cu and other elements is elevated, which means contact corrosion has occurred after elevation; see the following table for testing methods.
- It is recommended to add corrosion inhibitors to the antifreeze for maintenance and repair on a regular basis according to the requirements of the supplier.
Table 1 Recommended standards for coolant testing
项目 |
理化指标 |
|
颜色 |
显著颜色 |
|
外观 |
无异味,无沉淀,无悬浮物 |
|
冰点 |
-45℃(低温型) |
|
沸点 |
108℃(低温型) |
|
PH值 |
7-9 |
|
储备碱度 |
≥4 ml(有机配方) ≥9ml(含无机配方) |
|
总硬度 |
<120 mg/l |
|
主要元素含量 |
B |
<20mg/kg |
Si |
<20mg/kg |
|
P |
<20mg/kg |
|
Mo |
<20mg/kg |
|
Ca |
<20mg/kg |
|
Al3+ |
<50mg/L |
|
Fe2+ |
<50mg/L |
|
Cu2+ |
<50mg/L |
*Note: This is the water-cooled container parameter of CAC version 1.3, if your product is other manufacturers or other versions, it may be slightly different from this parameter, this parameter is for reference only.
If you have any questions, please feel free to contact BITMAIN Customer Support.