Table 1 Function description of the circuit breaker in the electric control box
Switch Components (No.) |
Function |
MCB17 |
Main switch of system control power supply and power supply of pumping station |
MCB18 |
The switch of the system control power supply, after the switch is powered on, the system has AC220V power supply |
MCB-DC1 |
The switch of the DC24V power supply in the system. After the switch is powered on, the sensor in the system can read the signal and upload it to the PLC; the touch screen is also powered on, and the system can be controlled from the touch screen. |
MCB-DC2 |
The switch of the DC12 power supply in the system. After the switch is powered on, the face recognition and door sensor in the system are powered on; the door can be opened by scanning the face. |
MCB-DC3 |
The switch of the DC5V power supply in the system. After the switch is powered on, the camera and main control module in the system are powered on. |
MSS6 |
The circuit breaker is a short-circuit protection switch at the front end of the inverter, mainly to prevent the inverter from overloading. |
MCB-31 |
The circuit breaker is the excitation coil switch in the electric control box responsible for disconnecting the MCB17. When the single circuit breaker is closed, the emergency stop button on the container door is pressed, the MCB17 is disconnected, and the electric control box is powered off. |
Table 2 Function description of circuit breakers in power distribution cabinet A
Switch Components (No.) |
Function |
MCB-A1 |
Main switch of power distribution cabinet A |
MCB-B1 |
Surge protector front protection switch |
MCB-15 |
Supply power to the switches in power distribution cabinet A |
MCB-21 |
Supply power to the meter in power distribution cabinet A |
MCB1-1~MCB7-15 |
Supply power to the computing unit on the side of the container |
MCB-30 |
The circuit breaker is the excitation coil switch in power distribution cabinet A responsible for disconnecting MCB-A1. When the single circuit breaker is turned on, the emergency stop button on the door of the power distribution cabinet or the container door is pressed, the MCB-A1 is disconnected, and the power distribution cabinet A is powered off |
Table 3 Function description of circuit breaker in power distribution cabinet B
Switch Components (No.) |
Function |
MCB-A2 |
Main switch of power distribution cabinet B |
MCB-B2 |
Surge protector front protection switch |
MCB-16 |
Supply power to the switches in power distribution cabinet B |
MCB-22 |
Supply power to the energy meter in power distribution cabinet B |
MCB8-1~MCB14-15 |
Power the computing unit on the other side of the container |
MCB-32 |
The circuit breaker is the excitation coil switch responsible for disconnecting MCB-A2 in power distribution cabinet B. When the single circuit breaker is turned on, the emergency stop button on the door B of the power distribution cabinet or the door of the container is pressed, the MCB-A2 is disconnected, and the power distribution cabinet B is powered off |
*Note: This is the water-cooled container parameter of AVIC 1.3 version. If your product is from other manufacturers or other versions, it may be slightly different from this parameter. This parameter is for reference only.