ANTRACK V1 specifications, power supply, hardware configuration, operating environment and other related information are shown in the table below :
|
Product Glance |
Value |
|
Model |
ANTRACK |
|
Version |
V1 |
|
Capacity |
4 units ANTMINER (S19 Hyd./S21 Hyd. series) |
|
Maximum load,kW |
24 |
|
Detailed Characteristics |
Value |
|
Hardware Configuration |
|
|
Size (Length*Width*Height), mm (without package) |
1000*600*2000 |
|
Size (Length*Width*Height), mm (with package) |
2380*1170*805 |
|
Net weight, kg (without package) |
205 |
|
Gross weight, kg (with package) |
310 |
| Network connection mode | EJ45 Ethernet 10/100M |
|
Power Supply |
|
|
Power supply AC Input voltage, Volt(1-1) |
380~415 |
|
Power supply AC Input Frequency Range, Hz |
50~60 |
|
Power supply AC Input current, Amp(1-2) |
80 |
|
Environment Requirements |
|
| Ambient temperature, °C |
15~45 |
| Water flow, L/min |
32.0~40.0 |
|
Water pressure, bar |
≤3.5 |
|
Working fluid (1-3) |
Antifreeze(10%) |
|
Liquid PH |
7.8~8.5 |
|
Storage temperature, °C |
-20~70 |
|
Operation humidity(non-condensing), RH |
10~90% |
Notes :
(1-1) Caution: Wrong input voltage may probably cause miner damaged
(1-2) Three-phase AC input.
(1-3) If the water conductivity is ≥100 μs/cm, the fluid must be replaced. The water conductivity is less than 20 μs/cm when the system is running at the first time.
If you have any questions, please feel free to contact BITMAIN Customer Support.
| < Contact us > |