AntSpace HK3 V2 Water-cooling Containers
Parameter Specifications
Water-cooling Antspace parameter specifications |
|||
Product Overview |
Input voltage, V |
415V±10%/60Hz/3P/N/PE |
|
Total power consumption, kW(Two power distribution cabinets share the load) |
≤1100 |
||
Miner |
Miner inlet/outlet water temperature, °C |
35/45 |
|
Container |
Supporting power consumption (cooling, power distribution), kW |
52 |
1000 |
Container dimension (length * width * height), mm |
6058*2438*2896 |
||
Cooling tower dimension (length*width*height), mm |
5800*2240*4286(Without guardrails, etc.) |
||
Weight, T (container with miner weight) |
12 |
||
Weight, T(Cooling tower operating weight) |
12 |
||
Number of miners |
210 |
||
Spray pump flow, m³/h |
230 |
||
Heat dissipation capacity, kW |
1000 |
||
Temperature variation between inlet and outlet(heating side)ΔT, ° |
10 |
||
Cooling tower docking interface specifications |
DN125 |
||
Heating docking interface specifications |
DN100 |
||
Cooling tower inlet water pipe specifications |
DN40 |
||
Cooling tower drainage pipe specifications |
DN65 |
||
Heating side pressure capacity, Kg |
10 |
||
Design flow of heating side, m³/h |
85 |
||
Maximum inlet/outlet water temperature on heating side, ℃ |
35/45 |
||
Heating side design ΔT |
40/50 |
||
Operating Environment Requirements |
Ambient temperature, °C |
-25~45 |
|
Noise, dB(A) |
78 (internal) / 65 (external) |
||
Internal coolant |
Antifreeze, Specifications are selected based on local environmental conditions |
||
Water Consumption, m³/h |
1.15(Water consumption of external spray, closed when the ambient temperature is below 10°C) |
Note: This is the water-cooling container parameter of AVIC 1.3 version. If your product is from another manufacturer or other version, it may be slightly different from this parameter. This parameter is for reference only.